Lodha NCP: Expert opinion from an international dry-wall specialist
|
Jan 19, 2019, 9:21 PM (2 days ago) | |
I have been involved in Senior
level management in the drywall industry both in South Africa and Europe for
over twenty years and would like to highlight certain items to you regarding
your drywall videos, more specifically titled “Lodha NCP punching holes in Dioro wall”
The use of drywall in a
residential tower would not be considered an unusual form of construction, it
would be standard in many countries, but alarmingly the construction of the
partitions in your video bring to light some questions relating to the gypsum
partitions shown, and the way they have been installed, if the partitions
have been installed correctly it would not have been so easy to punch through
them as there would be a steel support member at all the required positions
on the board (This is shown at minute 1.52 in this video)
There are very clear guidelines
from each manufacturer as to how the partitions should be installed, and when
followed correctly should provide a quality robust finish.
In the video you have shown, where
the horizontal joints of the boards are , there is a missing cross member in
the steel framing, this cross member is not only required for strength it is
required to enable the correct placement of the screw fixing at the centres
around the perimeter and joint of the board as specified by the
manufacturers.
This is not an optional
element in the partition framework it is expressly specified by the system
manufacturer. (This is also shown at 1.52 minutes into the video)
It is clearly visible at 1.58
minutes to 2.19 minutes in the “Busting Lodha wall” video that the
gypsum boards have been installed incorrectly. The gypsum boards on opposing
sides of the wall have not been staggered on alternate studs, this indicates
that the joints of the board are on the same stud on both sides of the wall.
This is contrary to all manufactures installation guidelines globally as it
diminishes the durability of the partition, and in a fire rated partition
assembly would be considered unacceptable.
Depending on the manufacturer the
specifications will change slightly but the theory remains the same , as this
is how the partitions will have been laboratory tested for fire and acoustic
properties.
Installation outside the
manufacturers guidelines is not recommended and diminishes the performance of
the partition in both fire rating and acoustic properties.
You mention that the material used
is Saint-Gobain (1.27),which is a leading manufacturer of construction
material , and in this case ,drywall board and metal suppler ,however it is a
prerequisite in the installation guide of this manufacturer that the screw
centres are at a maximum of 300mm, and have this noggin channel in place,
without this noggin channel the required fixing centres cannot be maintained,
and therefore the partition performance will be affected.
Has the noggin channel been missed
in this location or omitted totally throughout?? , as it does not appear to
be installed in either partition in any of the videos I have witnessed.
At 1.52 minutes into the first
video and .17 seconds in the 2nd video. It can be seen that no noggin channel
is in place.
The socket and switch installation
adheres to no manufacturers installation guidelines and as such meets no
standard as it appears to be a section of floor track that has been crudely
adapted to support a switch. As this is an untested method of installation it
is very unlikely that a leading brand of drywall material supply would accept
this as a quality installation of their product to support an electrical
outlet.
All manufacturers have a design
detail for installation of electrical outlets and this has not been followed
in the installation that you have presented.
My main concern would turn to the
installation of the fire compartmentation partitions of the building,
moreover ,this being the fire rated partitions and the shaft wall fire rated
partitions that form the passive fire protection throughout the building
through resistance to heat and flame and maintain the fire line for the
required time.
Partitions between flats, known
as party walls, and common areas like lift waiting areas/lobbies must carry a
severe duty rating, these partitions, when constructed correctly will provide
a fire resistance of 120 minutes, constructed incorrectly the resistance time
to fire is unknown.
It is clear from the video
(Titled, How safe are Lodha flats from thieves and moisture) that there is a
large hole through a fire rated drywall partition that forms what appears to
be a fire rated service riser that travels vertically outside (and somewhat)
inside the flat, there is no passive fire protection applied to this
penetration and the same location (this is shown at 1.15-1.20 minutes) does
not seem to have a fire rated door mounted in the opening to form the
fireline (this is shown at 0.44 seconds), it would be imperative that the fire
compartmentation here is maintained, if this is where the fireline is.
In this location, or any other
location where there are unknown or unplanned penetrations in a fire rated
partition like the one previously discussed, smoke and/or flame can pass
through this penetration into the void.
This makes the drywall fire rated
partition in this location obsolete as it is unable to provide the required
resistance, penetrations like this must be identified and sealed correctly.
Having penetrations in fire walls
like this permits the passage of fire from room to room within a flat, or
worse beyond the defined fire compartment.
Fire compartmentation is an
essential element in high rise construction and it is essential that it is
maintained and installed correctly, whether it is block/brick, fire stopping
or fire rated drywall partition.
Drywall fire compartmentation
drawings are used worldwide should be available to view on the plans of this
structure. With clearly defined fire lines.
Is this the case in other
locations also? This would need a full inspection from an independent
observer to guarantee that there have been no other exposed openings in
firewalls like the one in the video, not just in fire rated partitions but
block work and slab penetrations that go from floor to floor vertically.
From the video Titled Sewage pipes and fire hazards inside bedrooms
In relation to the room inside the
master bedroom from that carries sewer/water pipes vertically through the
building, it is important that the passage of fire cannot travel from flat to
flat. At 0.28 it shows the flat owner standing on a metal grate with penetrations,
a similar metal grate is shown at 1.28 above at the level of the upstairs
neighbors flat. In this location there is no passive fire protection
preventing transfer of fire to the adjoining flat.
Can you confirm that this is a
fire door on this sewer/water/service riser and how many flats are exposed
vertically like this? like There should be passive fire protection in the
form of a blockwork wall, fire rated partition or fire rated mortar between
each floor at slab level as passive fire protection to prevent the vertical
movement of fire throughout the structure.
My concern would be that a fire in
the master bedroom or anywhere in that flat could simply transfer to the
apartment above through this service duct as it is currently shown, or several
flats if there is no fire protection.
I would highlight these issues to
a fire officer that would be accountable in case of fire, unlike water , fire
does not give a second chance.
I would strongly recommend that
access is gained to the ceiling void above the false ceiling for the
following reasons, as they are commonly omitted, and by these omissions the
fire ratings of walls are compromised and acoustic properties are made
redundant.
1. Do the gypsum boards that are
on all partitions continue up to the slab level at the top and not just above
the level of the false ceiling. Otherwise there is free flow of smoke and
flame within the ceiling cavity.
2. Are there any penetrations in
the fire rated drywall partitions that have not been sealed and are hidden
within the ceiling void. If so these will accommodate the transmission of
fire and must be identified and addressed.
3. Has the metal ceiling
frame that supports the gypsum boards been installed to the manufacturers
guidelines, for example
4. Have the correct fixings been
used into the concrete slab, have the correct metal components been used in
the assembly, have the correct number of components been used in the assembly
and are the components at the correct centres to maintain the stability of
the ceiling frame. Have the correct number of metal to metal screw
fixings been used in the support hangers,
This is mandatory to maintain
ceiling performance, to prevent ceiling sag, and possibly ceiling failure. A
detailed independent review should be conducted on the actual installation of
the false ceilings and partitions and compared to the manufacturers
installation guidelines and an audit produced.
5. Importantly, have the correct
number of fixings been used in the correct locations to maintain the system
stability and have the correct fixings been used for each component.
Please note that on a previous
review on the ceiling installation in new cuffe the false ceilings had not
been installed to the manufacturers installation guidelines.
While requesting my privacy is
respected please be assured that I have detailed knowledge of the global
drywall industry and I have made several site visits to this particular
project , not just to one tower on the project but 3 towers in total in New
Cuffe parade.
The towers I attended had a
combination of different drywall material manufacturers, one particular tower
had an installation of unbranded metal components that were not being
installed to any drywall manufacturers guidelines and had not taken into
account even the basic principles of drywall partition assembly.
Components being used in an ad-hoc
untested manner that contravened drywall norms.
I believe the non compliance to
drywall partition installation guidelines, and possibly the inability of the
installation team has led to the resulting quality issues in NCP.
While Lodha maybe a big
brand, ultimately their quality can only be as good as the subcontractors that
they have used for the actual work. Having a large brand ambassador is all
good and well but does he know how the pipework has been installed and tested
and does he know the drywall has been installed and has the passive fire
protection been complete, although a fabulous cricketer, I would not like
Virat Koli to do the plumbing in my house.
So Krishnaraj, to conclude, it is
of dire importance that the fire related issues discussed are dealt with post
haste by a professional.
Should a similar issue relating to
fire safety arise in the UK, it would be standard procedure for the fire
authorities to do an inspection and if problems relating to fire safety were
found the whole tower would be evacuated, I have attached two links below to
validate this statement.
Regards,
Matthew Thomas
|
ReplyDeleteThis professional hacker is absolutely reliable and I strongly recommend him for any type of hack you require. I know this because I have hired him severally for various hacks and he has never disappointed me nor any of my friends who have hired him too, he can help you with any of the following hacks:
-Phone hacks (remotely)
-Credit repair
-Bitcoin recovery (any cryptocurrency)
-Make money from home (USA only)
-Social media hacks
-Website hacks
-Erase criminal records (USA & Canada only)
-Grade change
Email: cybergoldenhacker at gmail dot com
10 Months Chit Scheme
ReplyDeleteMonthly Chit Fund
Fantastic blog post! I just stumble upon this blog post and found it very useful and informative. I do agree with your opinions which are really very interesting.
ReplyDeletePainting Contractors in Louisville, TN
This integration includes linking everything from smoke alarms and fire sprinkler systems to security alarms and access control systems. Visit Now Fire Protection Integration
ReplyDeleteThis post is very useful to us thanks for sharing this info with us…
ReplyDeleteLex N Tax Associates has professional GST Refund Consultants in Delhi who assists businesses in efficiently managing and claiming their Goods and Services Tax refunds. They provide expert guidance on compliance, documentation, and timely filing to ensure smooth and maximum refunds. Their in-depth knowledge of GST regulations helps clients avoid delays and legal issues.
ReplyDeleteI found your article on Lodha NCP incredibly insightful! Your expert analysis captures the project’s unique features and potential impact on the local real estate market. The emphasis on amenities and community development is particularly noteworthy. Thanks for sharing such valuable information; it certainly helps prospective buyers make informed decisions!
ReplyDelete